Plastic shell circuit breaker FS-M6-10A~800A

The FSM6 series high voltage plastic shell circuit breaker (hereinafter referred to as the circuit breaker) is mainly used for distributing electrical energy and protecting overload, undervoltage, and short circuit protection of lines and power equipment in distribution networks with AC 50Hz (or 60Hz), rated insulation voltage of 1000V, rated working voltage of 1000V and below, and rated current of 800A and below. Under normal circumstances, it can be used for infrequent switching of circuits and infrequent starting of motors.
The product complies with IEC 60947-2 and GB/T 14048.2 standards.
  • Detailed introduction

normal condition

 

◆ Surrounding air temperature
The upper limit of the ambient air temperature is+40 ℃;
The lower limit of the ambient air temperature is -5 ℃;
The average temperature of the surrounding air within 24 hours shall not exceed+35 ℃.
◆ Altitude: The altitude of the installation site shall not exceed 2000m.
◆ Atmospheric conditions:
The relative humidity of the atmosphere shall not exceed 50% when the surrounding air temperature is+40 ℃; At lower temperatures, there can be higher relative humidity; The average maximum relative humidity in the wettest month is 90%,
At the same time, the monthly average minimum temperature for the month is+25 ℃, taking into account the condensation that occurs on the surface of the product due to temperature changes.
Pollution level: The pollution level is level 3.

 

Main technical parameters
Rated value of circuit breaker


Model: FSM 6-63M/125M/250M/400M/630M/800M
FSM 6-125H/250H/400H/630H/800H
Rated current of shell frame level (A): 63~800
Rated current (A): 10~800
Rated working voltage Ue (V): 400/690/1000
Rated insulation voltage Ui (V): 800/1000
Rated ultimate short-circuit breaking capacity (kA) 400V: 50 *~100
Rated operating short-circuit breaking capacity (kA) 400V: 35 *~65/10
Maintainable mechanical life (times): 10000/20000
Electrical life AC400V (times): 2000/3000
Number of poles: 3/4
Distance between flying 5 melons (mm): ≤ 50/≤ 100

 

Inverse time limit breaking action characteristics of overcurrent release for distribution circuit breakers when all poles are simultaneously energized
Test current name: Agreed non tripping current: 1.05I/in
Agreed time: 2h (In>63A), 1h (ln ≤ 63A)
Starting state: cold state
Test current name: Agreed tripping current: 1.30I/in
Agreed time: 2h (ln>63A), 1h (ln ≤ 63A)
Starting state: Immediately after Experiment One
Test current name: Instantaneous release 400/690V: 8/12 In
Agreed time: Breaking time<0.2 seconds
Test current name: Instantaneous release 800/1000V: 5/10 In
Agreed time: Breaking time<0.2 seconds

 

Inverse time limit breaking action characteristics of circuit breakers for motor protection when all poles of overcurrent release are simultaneously energized
1.0I/in - agreed time>2h - starting state - cold state
1.2I/in - agreed time ≤ 2h - starting state - starting immediately after test one
1.5I/in - agreed time ≤ 2min - starting state - hot state - note: In ≤ 25
≤ 8min - Starting state - Hot state - Remarks: 25A<In ≤ 800A
7.2I/in - Agreed time 0.5s ≤ T ≤ 5S - Starting state - Cold state - Remarks: In ≤ 25A
6s ≤ T ≤ 20s - Starting state - Cold state - Remarks: 25A<In ≤ 800A

 

Internal and external accessories of circuit breakers

 

Internal accessories of circuit breakers
◇ Undervoltage release
When the voltage drops (even slowly) to within the range of 70% and 35% of the rated voltage, the undervoltage release should act; Undervoltage release when the power supply voltage is lower than the release voltage
At 35%, the undervoltage release should be able to prevent the circuit breaker from closing; When the power supply voltage is equal to or greater than 85%, it should be possible to ensure that the circuit breaker is closed.
Special reminder: Circuit breakers equipped with undervoltage releases can only open and close normally when the undervoltage is at the rated voltage.

 

Rated voltage and frequency of undervoltage release

 

A2 voltage specification: AC230V
A2 rated frequency: 50Hz
A4 voltage specification: AC400V
A4 rated frequency: 50Hz
◇ Shunt release device
The circuit breaker can reliably disconnect at a rated voltage of 70%~110%

 

Rated voltage and frequency of shunt release

 

A2 voltage specification: AC230V
A2 rated frequency: 50Hz
A4 voltage specification: AC400V
A4 rated frequency: 50Hz
D3 voltage specification: DC24V
Note: When selecting DC24V voltage specification, the rated current reaches 5A ± 0.5.

Plastic shell circuit breaker FS-M6-10A~800A

The FSM6 series high voltage plastic shell circuit breaker (hereinafter referred to as the circuit breaker) is mainly used for distributing electrical energy and protecting overload, undervoltage, and short circuit protection of lines and power equipment in distribution networks with AC 50Hz (or 60Hz), rated insulation voltage of 1000V, rated working voltage of 1000V and below, and rated current of 800A and below. Under normal circumstances, it can be used for infrequent switching of circuits and infrequent starting of motors.
The product complies with IEC 60947-2 and GB/T 14048.2 standards.
  • 详细介绍

normal condition

 

◆ Surrounding air temperature
The upper limit of the ambient air temperature is+40 ℃;
The lower limit of the ambient air temperature is -5 ℃;
The average temperature of the surrounding air within 24 hours shall not exceed+35 ℃.
◆ Altitude: The altitude of the installation site shall not exceed 2000m.
◆ Atmospheric conditions:
The relative humidity of the atmosphere shall not exceed 50% when the surrounding air temperature is+40 ℃; At lower temperatures, there can be higher relative humidity; The average maximum relative humidity in the wettest month is 90%,
At the same time, the monthly average minimum temperature for the month is+25 ℃, taking into account the condensation that occurs on the surface of the product due to temperature changes.
Pollution level: The pollution level is level 3.

 

Main technical parameters
Rated value of circuit breaker


Model: FSM 6-63M/125M/250M/400M/630M/800M
FSM 6-125H/250H/400H/630H/800H
Rated current of shell frame level (A): 63~800
Rated current (A): 10~800
Rated working voltage Ue (V): 400/690/1000
Rated insulation voltage Ui (V): 800/1000
Rated ultimate short-circuit breaking capacity (kA) 400V: 50 *~100
Rated operating short-circuit breaking capacity (kA) 400V: 35 *~65/10
Maintainable mechanical life (times): 10000/20000
Electrical life AC400V (times): 2000/3000
Number of poles: 3/4
Distance between flying 5 melons (mm): ≤ 50/≤ 100

 

Inverse time limit breaking action characteristics of overcurrent release for distribution circuit breakers when all poles are simultaneously energized
Test current name: Agreed non tripping current: 1.05I/in
Agreed time: 2h (In>63A), 1h (ln ≤ 63A)
Starting state: cold state
Test current name: Agreed tripping current: 1.30I/in
Agreed time: 2h (ln>63A), 1h (ln ≤ 63A)
Starting state: Immediately after Experiment One
Test current name: Instantaneous release 400/690V: 8/12 In
Agreed time: Breaking time<0.2 seconds
Test current name: Instantaneous release 800/1000V: 5/10 In
Agreed time: Breaking time<0.2 seconds

 

Inverse time limit breaking action characteristics of circuit breakers for motor protection when all poles of overcurrent release are simultaneously energized
1.0I/in - agreed time>2h - starting state - cold state
1.2I/in - agreed time ≤ 2h - starting state - starting immediately after test one
1.5I/in - agreed time ≤ 2min - starting state - hot state - note: In ≤ 25
≤ 8min - Starting state - Hot state - Remarks: 25A<In ≤ 800A
7.2I/in - Agreed time 0.5s ≤ T ≤ 5S - Starting state - Cold state - Remarks: In ≤ 25A
6s ≤ T ≤ 20s - Starting state - Cold state - Remarks: 25A<In ≤ 800A

 

Internal and external accessories of circuit breakers

 

Internal accessories of circuit breakers
◇ Undervoltage release
When the voltage drops (even slowly) to within the range of 70% and 35% of the rated voltage, the undervoltage release should act; Undervoltage release when the power supply voltage is lower than the release voltage
At 35%, the undervoltage release should be able to prevent the circuit breaker from closing; When the power supply voltage is equal to or greater than 85%, it should be possible to ensure that the circuit breaker is closed.
Special reminder: Circuit breakers equipped with undervoltage releases can only open and close normally when the undervoltage is at the rated voltage.

 

Rated voltage and frequency of undervoltage release

 

A2 voltage specification: AC230V
A2 rated frequency: 50Hz
A4 voltage specification: AC400V
A4 rated frequency: 50Hz
◇ Shunt release device
The circuit breaker can reliably disconnect at a rated voltage of 70%~110%

 

Rated voltage and frequency of shunt release

 

A2 voltage specification: AC230V
A2 rated frequency: 50Hz
A4 voltage specification: AC400V
A4 rated frequency: 50Hz
D3 voltage specification: DC24V
Note: When selecting DC24V voltage specification, the rated current reaches 5A ± 0.5.

Plastic shell circuit breaker FS-M6-10A~800A

The FSM6 series high voltage plastic shell circuit breaker (hereinafter referred to as the circuit breaker) is mainly used for distributing electrical energy and protecting overload, undervoltage, and short circuit protection of lines and power equipment in distribution networks with AC 50Hz (or 60Hz), rated insulation voltage of 1000V, rated working voltage of 1000V and below, and rated current of 800A and below. Under normal circumstances, it can be used for infrequent switching of circuits and infrequent starting of motors.
The product complies with IEC 60947-2 and GB/T 14048.2 standards.
  • Detailed introduction

normal condition

 

◆ Surrounding air temperature
The upper limit of the ambient air temperature is+40 ℃;
The lower limit of the ambient air temperature is -5 ℃;
The average temperature of the surrounding air within 24 hours shall not exceed+35 ℃.
◆ Altitude: The altitude of the installation site shall not exceed 2000m.
◆ Atmospheric conditions:
The relative humidity of the atmosphere shall not exceed 50% when the surrounding air temperature is+40 ℃; At lower temperatures, there can be higher relative humidity; The average maximum relative humidity in the wettest month is 90%,
At the same time, the monthly average minimum temperature for the month is+25 ℃, taking into account the condensation that occurs on the surface of the product due to temperature changes.
Pollution level: The pollution level is level 3.

 

Main technical parameters
Rated value of circuit breaker


Model: FSM 6-63M/125M/250M/400M/630M/800M
FSM 6-125H/250H/400H/630H/800H
Rated current of shell frame level (A): 63~800
Rated current (A): 10~800
Rated working voltage Ue (V): 400/690/1000
Rated insulation voltage Ui (V): 800/1000
Rated ultimate short-circuit breaking capacity (kA) 400V: 50 *~100
Rated operating short-circuit breaking capacity (kA) 400V: 35 *~65/10
Maintainable mechanical life (times): 10000/20000
Electrical life AC400V (times): 2000/3000
Number of poles: 3/4
Distance between flying 5 melons (mm): ≤ 50/≤ 100

 

Inverse time limit breaking action characteristics of overcurrent release for distribution circuit breakers when all poles are simultaneously energized
Test current name: Agreed non tripping current: 1.05I/in
Agreed time: 2h (In>63A), 1h (ln ≤ 63A)
Starting state: cold state
Test current name: Agreed tripping current: 1.30I/in
Agreed time: 2h (ln>63A), 1h (ln ≤ 63A)
Starting state: Immediately after Experiment One
Test current name: Instantaneous release 400/690V: 8/12 In
Agreed time: Breaking time<0.2 seconds
Test current name: Instantaneous release 800/1000V: 5/10 In
Agreed time: Breaking time<0.2 seconds

 

Inverse time limit breaking action characteristics of circuit breakers for motor protection when all poles of overcurrent release are simultaneously energized
1.0I/in - agreed time>2h - starting state - cold state
1.2I/in - agreed time ≤ 2h - starting state - starting immediately after test one
1.5I/in - agreed time ≤ 2min - starting state - hot state - note: In ≤ 25
≤ 8min - Starting state - Hot state - Remarks: 25A<In ≤ 800A
7.2I/in - Agreed time 0.5s ≤ T ≤ 5S - Starting state - Cold state - Remarks: In ≤ 25A
6s ≤ T ≤ 20s - Starting state - Cold state - Remarks: 25A<In ≤ 800A

 

Internal and external accessories of circuit breakers

 

Internal accessories of circuit breakers
◇ Undervoltage release
When the voltage drops (even slowly) to within the range of 70% and 35% of the rated voltage, the undervoltage release should act; Undervoltage release when the power supply voltage is lower than the release voltage
At 35%, the undervoltage release should be able to prevent the circuit breaker from closing; When the power supply voltage is equal to or greater than 85%, it should be possible to ensure that the circuit breaker is closed.
Special reminder: Circuit breakers equipped with undervoltage releases can only open and close normally when the undervoltage is at the rated voltage.

 

Rated voltage and frequency of undervoltage release

 

A2 voltage specification: AC230V
A2 rated frequency: 50Hz
A4 voltage specification: AC400V
A4 rated frequency: 50Hz
◇ Shunt release device
The circuit breaker can reliably disconnect at a rated voltage of 70%~110%

 

Rated voltage and frequency of shunt release

 

A2 voltage specification: AC230V
A2 rated frequency: 50Hz
A4 voltage specification: AC400V
A4 rated frequency: 50Hz
D3 voltage specification: DC24V
Note: When selecting DC24V voltage specification, the rated current reaches 5A ± 0.5.

Fisco Electric (Shenzhen) Co., Ltd

Contact phone number: 400-990-0152
Address: No. 8 Shenlian Road, Henggang Street, Longgang District, Shenzhen, Guangdong Province
Service philosophy: Service with dedication, quality first, and customer satisfaction.

Fisco Electric (Shenzhen) Co., Ltd

Contact phone number: 400-990-0152
Address: No. 8 Shenlian Road, Henggang Street, Longgang District, Shenzhen, Guangdong Province
Service philosophy: Service with dedication, quality first, and customer satisfaction.

Technical support: NetTrade Media Technology

Copyright ©  Copyright 2024 Fisco Electric (Shenzhen) Co., Ltd

Fisco Electric (Shenzhen) Co., Ltd

Service hotline: 400-990-0152
Company address: No. 8 Shenlian Road, Henggang Street, Longgang District, Shenzhen, Guangdong Province
Service philosophy: Service with dedication, quality first, and customer satisfaction.

Technical support: Online Trade Media Technology Record No.: Zhejiang ICP Bei 2020035851

Copyright ©  Copyright 2024 Fisco Electric (Shenzhen) Co., Ltd

Copyright © 2024 Fishman Electric (Shenzhen) Co., Ltd

备案号:粤ICP备2024305252号-1